Email

SQD 31114 NON-AUTOMATIC MOLDED CASE

Manufacturer: Square-D / Schneider | Catalog # 31114 | Cooper Electric Part # 838352

$1,635.00 /ea
ea
Log in or register to view your price, purchase history, and more!
Out of stock, please contact your sales representative for availability, pricing and lead times
CA Prop65 Warning CA Prop65 Warning Product Spec Sheet
This Compact INS630 is a 3 poles non-automatic switch-disconnector with black rotary handle. It is suitable for isolation with positive contact indication, as defined by IEC 60947-1 and IEC60947-3 standards. The operational current is 630A at 415VAC in c

Technical Information

Actuator
DIRECT FRONT ROTARY HANDLE
Amperage
AC-22A 630 Amp AC 50/60 HZ 220/240 V-AC-23A 630 Amp AC 50/60 HZ 480 V NEMA-AC-23A 630 Amp AC 50/60 HZ 500/525 V-AC-23A 630 Amp AC 50/60 HZ 660/690 V-DC-22A 550 Amp DC 125 V 2 POLES IN SERIES-DC-23A 550 Amp DC 125 V 2 POLES IN SERIES-DC-23B 630 Amp DC 125 V 2 POLES IN SERIES-AC-22A 630 Amp AC 50/60 HZ 380/415 V-AC-22A 630 Amp AC 50/60 HZ 440/480 V-AC-22A 630 Amp AC 50/60 HZ 480 V NEMA-AC-22A 630 Amp AC 50/60 HZ 500/525 V-AC-22A 630 Amp AC 50/60 HZ 660/690 V-AC-23A 630 Amp AC 50/60 HZ 220/240 V-AC-23A 630 Amp AC 50/60 HZ 380/415 V-AC-23A 630 Amp AC 50/60 HZ 440/480 V
Applications
INS320...630
Number of Poles
3 Pole
Operating Temperature
-25-70 Adegrees C
Type
SWITCH DISCONNECTOR
Voltage
125 Volt DC-690 Volt AC 50/60 HZ

Manufacturer Information

Brand
Square D
Sub Brand
COMPACT INS,INTERPACT INS630,INTERPACT INS630

General Product Info

12-Digit UPC
785901680321
GTiN
03303430311140
Product UPC
78590168032

Dimensions

Depth
4.72 in
Height
205 mm
Length
130 mm
Warranty Length
18 mth
Width
7.28 in

Certifications and Compliance

CA Prop65 Warning
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go t
Country of Origin
USA
Mounting Support
  • rail
  • plate
Uimp Rated Impulse Withstand Voltage
  • 8 kV
  • 8 kVIEC 60947-3
Prop 65
  • WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go t
Carbon Footprint Of The Installation Phase A5
  • 0.24257003897211846
  • 0.2 kg CO2 eq.
Carbon Footprint Of The End Of Life Phase C1 To C4
  • 8 kg CO2 eq.
  • 8.15020406936328
Standards
  • IEC 60947-3
  • IEC 60947-1
Ue Rated Operational Voltage
  • 125 V DC
  • 690 V AC 50/60 Hz
Ui Rated Insulation Voltage
  • 800 V AC 50/60 Hz
Icm Rated Short Circuit Making Capacity
  • 330 kA with upstream protection circuit breaker 690 V AC 50/60 Hz
  • 330 kA with upstream protection circuit breaker 690 V AC
Ip Degree Of Protection
  • IP40 conforming to IEC 60529
Carbon Footprint Of The Manufacturing Phase A1 To A3
  • 31 kg CO2 eq.
  • 31.344424706838133
Electrical Durability
  • AC-22A 1500 cycles 440 V AC 50/60 Hz
  • AC-22A 1500 cycles 500 V AC 50/60 Hz
  • AC-22A 1500 cycles 500 V AC 50/6
Carbon Footprint Of The Use Phase B2 B3 B4 B6
  • 826 kg CO2 eq.
  • 825.8719853487119
Carbon Footprint Of The Distribution Phase A4
  • 0.6959527418786262
  • 0.7 kg CO2 eq.
Ith Conventional Free Air Thermal Current
  • 630 A 60 °C
Network Type
  • AC
  • DC
Ie Rated Operational Current
  • AC-22A 630 A AC 50/60 Hz 220/240 V
  • AC-22A 630 A AC 50/60 Hz 380/415 V
  • AC-22A 63
Icw Rated Short Time Withstand Current
  • 11.5 kA 3 s IEC 60947-3
  • 20 kA 1 s IEC 60947-3
  • 4 kA 30 s IEC 60947-3
  • 4.9 kA 20 s IEC 60947-3
  • 4.
Maximum Power
  • AC-23 200 kW 220/240 V AC 50/60 Hz
  • AC-23 200 kW 230 V AC 50/60 Hz NEMA)
  • AC-23
Product Certifications
  • CCC
  • KEMA-KEUR