Image thumbnail 1
Image thumbnail 2
Image thumbnail 3
Image thumbnail 4
Image thumbnail 5
Image thumbnail 6

Email

Square D LGP36400U31X Powerpact 3-Pole 400 Amp Molded Case Circuit Breaker

Manufacturer: Square-D / Schneider | Catalog # LGP36400U31X | Cooper Electric Part # 776126

$5,081.00/ea
ea
Log in or register to view your price, purchase history, and more!
Out of stock, please contact your sales representative for availability, pricing and lead times
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 400A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3 trip unit and an LI function. This unit has terminal nuts on the line side and lugs on the load side. This circuit breaker has a continuous current rating of 80%. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.

Technical Information

Amperage
400 Amp
Applications
Distribution
Conductor Size
2/0 AWG-500 kcmil
Control Type
Toggle
Frame
G
Interrupt Rating
18, 35, 65 kAIC
Line Rated Current
400-400 A
Mounting Type
Unit Mount Lug)
Net Weight
6.2 kg
Number of Poles
3 Pole
Range
PowerPact
Standard
CSA,IEC 60947-2,NEMA,NOM-003-SCFI-2000,UL
Storage Temperature
-50-85 degrees C
Strip Length
31 mm
TC Connection
AWG 2/0...500 KCMIL ALUMINIUM/COPPER)2,TERMINAL NUT LINE-LUGS LOAD
Terminal Type
AL600LS52K3
Trip Range
400 A
Trip Type
ELECTRONIC, STANDARD, MICROLOGIC 3.3, LI
Type
Circuit breaker
Voltage
600 Volt
Wire Size
AWG 2/0...500 kcmil aluminium/copper)2

Manufacturer Information

Brand
Square D
Sub Brand
L-Frame

General Product Info

12-Digit UPC
785901639824
Color
Black
GTiN
00785901639824
Product UPC
78590163982
Weight
6.2 kg

Dimensions

Depth
4.33 in
Height
13.39 in
Length
31 mm
Warranty Length
18 mth
Width
5.51 in

Certifications and Compliance

CA Prop65 Warning
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go t
Certifications
CSA,NOM,UL
Country of Origin
Mexico
IP Degree Of Protection
  • front cover IP40
Mounting Mode
  • unit mount lug)
Prop 65
  • WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go t
Carbon Footprint Of The Installation Phase A5
  • 1.8967904693791804
  • 2 kg CO2 eq.
Carbon Footprint Of The End Of Life Phase C1 To C4
  • 10 kg CO2 eq.
  • 10.302971150240523
Electrical Connection
  • terminal nut, line
  • lugs, load
ICS Rated Service Breaking Capacity
  • 65 kA 220/240 V AC 50/60 Hz IEC 60947-2
  • 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2
  • 35 kA 380/
Related Products
  • S29450
  • S29452
  • S29272
  • S434202
Carbon Footprint Of The Manufacturing Phase A1 To A3
  • 44 kg CO2 eq.
  • 43.82880551360121
UI Rated Insulation Voltage
  • 750 V IEC 60947-2
Accessories
  • S29386
  • VTRIPL
  • S29390
  • VTRIPL05
  • S29382
  • VTRIPL10
Market Segmentation
  • Commercial
  • Industrial
Persona Type Names
  • End User
  • Contractor
  • Original Equipment Manufacturer
  • OEM - Control Panelbuilder
  • Panel Builder
  • Electrician
  • System Integrator
Carbon Footprint Of The Use Phase B2 B3 B4 B6
  • 738 kg CO2 eq.
  • 738.058452197221
Number Of Slots
  • 2 auxiliary switch OF plug-in)
  • 1 alarm switch SD plug-in)
  • 1 overcurrent trip swi
Accessory Products
  • S29386
  • VTRIPL
  • S29390
  • VTRIPL05
  • S29382
  • VTRIPL10
Persona Type Ids
  • EU
  • LC
  • OM
  • OM8
  • PB
  • SC
  • SI
Auxiliaries
  • S29450
  • S29452
  • S29272
Carbon Footprint Of The Distribution Phase A4
  • 1.966271580566898
  • 2 kg CO2 eq.
Tightening Torque
  • 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
Operating Altitude
  • < 6561.68 ft (2000 m) without derating
  • 5000 m with derating
Suitability For Isolation
  • yes IEC 60947-2
AWG Gauge
  • 2 x AWG 2/0...500 kcmil aluminium/copper
Trip Unit Technology
  • electronic, standard, MicroLogic 3.3, LI
Market Segmentation Id
  • COMMERCIAL
  • INDUSTRIAL
Local Signalling
  • ready 1 LED green)
  • alarm 1 LED 90 % Ir orange)
  • alarm LED 105 % Ir red)
  • alarm LED 105 % Ir
UE Rated Operational Voltage
  • 600 V AC 50/60 Hz IEC 60947-3
Product Certifications
  • UL
  • CSA
  • NOM
UIMP Rated Impulse Withstand Voltage
  • 8 kV IEC 60947-2



Compare