Product image for Square D XENC1111 40 mm 240 VAC 3 Amp 1NO Pendant Station Contact Block
Image thumbnail 0
Image thumbnail 1
Image thumbnail 2

Email

Square D XENC1111 40 mm 240 VAC 3 Amp 1NO Pendant Station Contact Block

Manufacturer: Square-D / Schneider | Catalog # XENC1111 | Cooper Electric Part # 767602

$20.14 /ea
ea
Log in or register to view your price, purchase history, and more!
Out of stock, please contact your sales representative for availability, pricing and lead times
This Harmony XENC1111 is a spring return contact block 1 NO front mounting, 30 or 40mm centres. It is part of the range Harmony XAC pendant control stations for diameter 22mm plastic signaling units. It is designed for single speed applications.

Technical Information

Amperage
10 Amp
Applications
Control circuit;Single speed;XACM;XACB
Contact Configuration
1 NO
Contact Rating
Slow-break
Net Weight
0.02 kg
Operating Temperature
-25-70 Adegrees C
Standard
CSA C22.2 No 14,EN 60947-5-1,IEC 60947-5-1
Storage Temperature
-40-70 degrees C
TC Connection
SCREW CLAMP TERMINALS, 1 X 2.5 MMA WITH OR WITHOUT CABLE END-SCREW CLAMP TERMINALS, 2 X 1.5 MMA WITH OR WITHOUT CABLE END
Type
Single;Contact block;Spring return
Wattage
42 Watt DC-13 1000000 CYCLES 60 CYC/MN 120 Volt 0.5 INDUCTIVE IEC 60947 - 5-1 APPENDIX C-45 Watt DC-13 1000000 CYCLES 60 CYC/MN 48 Volt 0.5 INDUCTIVE IEC 60947 - 5-1 APPENDIX C-60 Watt DC-13 1000000 CYCLES 60 CYC/MN 24 Volt 0.5 INDUCTIVE IEC 60947 - 5-1 APPENDIX C

Manufacturer Information

Brand
Schneider Electric
Sub Brand
XENC

General Product Info

12-Digit UPC
389110643001
GTiN
03389110643008
Product UPC
78590164300
Weight
0.02 kg

Dimensions

Warranty Length
18 mth

Certifications and Compliance

CA Prop65 Warning
WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Country of Origin
Czechia
Connections Terminals
  • screw clamp terminals, 1 x 2.5 mm² with or without cable end
  • screw clamp terminals, 2 x 1.5 mm² with or without cable end
Prop 65
  • WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Carbon Footprint Of The Installation Phase A5
  • 0.0021681816352577873
  • 0 kg CO2 eq.
Carbon Footprint Of The End Of Life Phase C1 To C4
  • 0 kg CO2 eq.
  • 0.043903888608778766
Carbon Footprint Of The Manufacturing Phase A1 To A3
  • 0.2 kg CO2 eq.
  • 0.154518741690819
UI Rated Insulation Voltage
  • 500 V 3)IEC 60947-1
Rated Operational Power In W
  • 42 W DC-13 1000000 cycles 60 cyc/mn 120 V 0.5 inductive IEC 60947-5-1 appendix C
  • 45 W DC-13 1000000 cycles 60 cyc/mn 48 V 0.5 inductive IEC 60947-5-1 appendix C
  • 60 W DC-13 1000000 cycles 60 cyc/mn 24 V 0.5 inductive IEC 60947-5-1 appendix C
Vibration Resistance
  • 15 gn (f= 10-500 Hz) conforming to IEC 60068-2-6
Market Segmentation
  • Commercial
  • Industrial
Terminal Identifier
  • (13-14)NO
  • (11-12)NC
Persona Type Names
  • Charge Point Operator
  • End User
  • Contractor
  • Original Equipment Manufacturer
  • OEM - Control Panelbuilder
  • Panel Builder
  • Electrician
  • System Integrator
  • IT Channel Partner
Carbon Footprint Of The Use Phase B2 B3 B4 B6
  • 0 kg CO2 eq.
  • 0
Persona Type Ids
  • BM9
  • EU
  • LC
  • OM
  • OM8
  • PB
  • SC
  • SI
  • VR
Carbon Footprint Of The Distribution Phase A4
  • 0.01624309204189662
  • 0 kg CO2 eq.
Short Circuit Protection
  • 10 A fuse protection cartridge gG
Rated Operational Power In VA
  • 140 VA AC-15 1000000 cycles 60 cyc/mn 24 V 50/60 Hz 0.5 inductive
  • 385 VA AC-15 1000000 cycles 60 cyc/mn 48 V 50/60 Hz 0.5 inductive
  • 455 VA AC-15 1000000 cycles 60 cyc/mn 230 V 50/60 Hz 0.5 inductive
  • 525 VA AC-15 1000000 cycles 60 cyc/mn 127 V 50/60 Hz 0.5 inductive
Contact Code Designation
  • A300 AC-15, Ue = 240 V, Ie = 3 A IEC 60947-5-1 appendix A
  • Q300 DC-13, Ue = 250 V, Ie = 0.27 A IEC 60947-5-1 appendix A
Market Segmentation Id
  • COMMERCIAL
  • INDUSTRIAL
Shock Resistance
  • 100 gn IEC 60068-2-27
UIMP Rated Impulse Withstand Voltage
  • 6 kV IEC 60947-1



Compare