Product image for SQD S6200A0A0B0A0A0R ION6200 meter
Image thumbnail 0
Image thumbnail 1
Image thumbnail 2

Email

SQD S6200A0A0B0A0A0R ION6200 meter

Manufacturer: Square-D / Schneider | Catalog # S6200A0A0B0A0A0R | Cooper Electric Part # 669562

$1,500.00 /ea
ea
Log in or register to view your price, purchase history, and more!
Out of stock, please contact your sales representative for availability, pricing and lead times
CA Prop65 Warning CA Prop65 Warning Product Spec Sheet
ION6200 meter (all measurmt) - w/display 240VAC/300VDC - std com - w pwd

Technical Information

Accuracy
CLASS 0.5 POWER IEC 60687-CLASS 0.5 ENERGY IEC 60687-CLASS 0.5 POWER ANSI C12.20-CLASS 0.5 ENERGY ANSI C12.20,CURRENT 0.3 -VOLTAGE 0.3 -POWER +/- 0.5 -FREQUENCY +/- 0.1 -POWER FACTOR +/- 1 -ENERGY +/- 0.5
Amperage
10 Amp
Applications
INDOOR,METERING
Display Type
7 Segments LED + Decimal Point
Indicator
7 SEGMENTS LED + DECIMAL POINT
Number of Outputs
0
Output
0
Size
110 MM,110 MM,65 MM
Type
APPARENT POWER TOTAL-APPARENT POWER PER PHASE-CURRENT-VOLTAGE-FREQUENCY-HARMONIC DISTORSION (I THD & U THD)-ACTIVE AND REACTIVE POWER TOTAL-ACTIVE AND REACTIVE ENERGY-APPARENT ENERGY-POWER FACTOR-DEMAND CURRENT (I1, I2, I3, IG)-ACTIVE AND REACTIVE POWER PER PHASE,ENERGY AND POWER QUALITY METER
Voltage
100...240 Volt AC 50/60 HZ-110...300 Volt DC

Manufacturer Information

Brand
Square D
Sub Brand
ION6200,POWERLOGIC ION6200

General Product Info

12-Digit UPC
785901679141
GTiN
00785901679141
Product UPC
78590167914

Dimensions

Depth
2.56 in
Height
4.33 in
Warranty Length
18 mth
Width
4.33 in

Certifications and Compliance

CA Prop65 Warning
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Prop 65
  • WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Standards
  • CSA 1010-1
  • EN 61010-1
  • UL 3111-1
Communication Port Support
  • screw terminal block RS485 isolated
Ip Degree Of Protection
  • IP65 front:
  • IP30 back:
Communication Port Protocol
  • Modbus RTU, master 19200 bauds
  • ION
Type Of Measurement
  • apparent power total
  • apparent power per phase
  • current
  • voltage
  • frequency
  • harmonic distortion (I THD & U THD)
  • active and reactive power total
  • active and reactive energy
  • apparent
Electromagnetic Compatibility
  • electrostatic discharge immunity test conforming to IEC 61000-4-2
  • immunity to radiated fields conforming to IEC 61000-4-3
  • immunity t
Us Rated Supply Voltage
  • 100...240 V AC 50/60 Hz
  • 110...300 V DC
Measurement Accuracy
  • current 0.3 %
  • voltage 0.3 %
  • power +/- 0.5 %
  • frequency +/- 0.1 %
  • power factor +/- 1 %
  • energy +/- 0.5 %
Measurement Voltage
  • 60-400 V AC 50-60 Hz between phase and neutral
  • 103.5-690 V AC 50-60 Hz between phases
  • 103.5-690 V AC 50-60 Hz bet
Network Frequency
  • 50 Hz
  • 60 Hz
Poles Description
  • 3P
  • 3P + N
  • 2P + N
Product Certifications