Appleton EYF-75 3/4" Explosion Proof Sealing Unilet

Manufacturer: Appleton Electric | Catalog # EYF-75 | Cooper Electric Part # 59257

$37.43 /ea
ea
Log in or register to view your price, purchase history, and more!
Out of stock, please contact your sales representative for availability, pricing and lead times
Appleton™ EY 25% fill vertical and horizontal conduit sealing fittings prevent the passage of gases, vapors or flames from one portion of a conduit system to another. They also restrict large amounts of ignitable gases or vapors from accumulating to confine explosive pressure. Appleton sealing fittings are explosionproof, dust-ignitionproof and raintight. They are suitable for use in Class I and II locations.

Technical Information

Applications
For Use With Threaded Rigid Metal Conduit and IMC
Hub Size
3/4 in
Material
Iron
Size
3/4 IN
TC Connection
Female Threaded
Trade Size
3/4 Inch
Type
25% Fill Vertical and Horizontal, Explosionproof, Female

Manufacturer Information

Brand
Appleton
Sub Brand
Unilet

General Product Info

12-Digit UPC
781381135122
Color
Gray
Finish
Zinc
GTiN
00781381135122
Product Series
ENY
Product UPC
78138113512
Used With
Threaded Rigid Metal Conduit and IMC
Weight
0.55 lb

Dimensions

Height
0.1 in
Length
5 in
Width
10 in
Features
  • Explosionproof, dust-ignitionproof, raintight
  • Prevent passage of gases, vapors or flames from one portion of conduit system to another. Restrict any explosion to the sealed off enclosure. Prevent pressure piling within conduit system
  • Required in Class I, Division 1 and 2 locations within 18\" of enclosures containing apparatus that may cause arcs, sparks or high temperatures
  • Required in Class I, Division 1 and 2 locations where 2\" or larger conduit enters enclosure, fitting housing terminals, splices or taps
  • Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
  • Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36\" or less conduit. Seal must be located within 18\" of either enclosure
  • Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in Class I, Division 2 locations
  • Smooth, rounded integral bushing in each hub protects conductor insulation
  • Accurately tapped, tapered threads for tight, rigid joints and ground continuity
  • Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
  • UL Listed for use with Kwiko™ A Sealing Compound. Also listed with certain competitors sealing cement, contact factory for details
  • Close radius type for sealing vertical or horizontal conduit runs