Product image for Square D XESD1281 600 VAC 10 Amp 2NO 1NC Spring Return Pendant Station Contact
Image thumbnail 0
Image thumbnail 1
Image thumbnail 2

Email

Square D XESD1281 600 VAC 10 Amp 2NO 1NC Spring Return Pendant Station Contact

Manufacturer: Square-D / Schneider | Catalog # XESD1281 | Cooper Electric Part # 549366

$186.00 /ea
ea
Log in or register to view your price, purchase history, and more!
Out of stock, please contact your sales representative for availability, pricing and lead times
This Harmony XAC, double contact block uses screw-clamp terminals and has 1 x NO + 1 changeover contact SPDT single pole double throw. This contact block allows fast and easy replacement and configuration of your push buttons and selector switches. It is easily installed and replaced on XACM and XACB pendant control stations and connects to control circuits with simple screw-clamp connections. It protects operators from unexpected contact with live circuits thanks to its IP20 protection index. It has clear labelling of the contact wiring and terminals names on the side of the block. Vibration resistant screw clamp connection terminals ensure high vibration resistance making product suitable installation on high impact machine.

Technical Information

Action
Staggered;Snap action
Actuator
2 spring return
Amperage
10 Amp
Applications
2-speed;XACB;XACM
Contact Configuration
1 C/O + 1 NO
Net Weight
0.19 kg
Operating Force
15 N
Operating Temperature
-25-70 Adegrees C
Standard
CSA C22.2 No 14,EN 60947-5-1,IEC 60947-5-1
Storage Temperature
-40-70 degrees C
TC Connection
SCREW CLAMP TERMINALS, 1 X 2.5 MMA WITH OR WITHOUT CABLE END-SCREW CLAMP TERMINALS, 2 X 1.5 MMA WITH OR WITHOUT CABLE END
Type
Double;Contact block
Voltage
500 Volt
Wattage
140 Watt DC-13 1000000 CYCLES 60 CYC/MN 24 Volt 0.5 INDUCTIVE IEC 60947 - 5-1 APPENDIX C-140 Watt DC-13 1000000 CYCLES 60 CYC/MN 48 Volt 0.5 INDUCTIVE IEC 60947 - 5-1 APPENDIX C-95 Watt DC-13 1000000 CYCLES 60 CYC/MN 120 Volt 0.5 INDUCTIVE IEC 60947 - 5-1 APPENDIX C

Manufacturer Information

Brand
Schneider Electric
Sub Brand
HARMONY XAC

General Product Info

12-Digit UPC
389110641106
GTiN
03389110641103
Product UPC
78590164110
Weight
0.19 kg

Dimensions

Warranty Length
18 mth

Certifications and Compliance

CA Prop65 Warning
WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Country of Origin
Czechia
Connections Terminals
  • screw clamp terminals, 1 x 2.5 mm² with or without cable end
  • screw clamp terminals, 2 x 1.5 mm² with or without cable end
Prop 65
  • WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Carbon Footprint Of The Installation Phase A5
  • 0.0008947129
  • 0 kg CO2 eq.
Carbon Footprint Of The End Of Life Phase C1 To C4
  • 0.2 kg CO2 eq.
  • 0.1621013986
Carbon Footprint Of The Manufacturing Phase A1 To A3
  • 0.9 kg CO2 eq.
  • 0.8885893551
Electrical Shock Protection Class
  • class II conforming to IEC 61140
UI Rated Insulation Voltage
  • 500 V 3)IEC 60947-1
Rated Operational Power In W
  • 140 W DC-13 1000000 cycles 60 cyc/mn 24 V 0.5 inductive IEC 60947-5-1 appendix C
  • 140 W DC-13 1000000 cycles 60 cyc/mn 48 V 0.5 inductive IEC 60947-5-1 appendix C
  • 95 W DC-13 1000000 cycles 60 cyc/mn 120 V 0.5 inductive IEC 60947-5-1 appendix C
Vibration Resistance
  • 15 gn (f= 10-500 Hz) conforming to IEC 60068-2-6
Market Segmentation
  • Commercial
  • Industrial
Terminal Identifier
  • (13-14)NO
  • (11-12)NC
Persona Type Names
  • Charge Point Operator
  • End User
  • Contractor
  • Original Equipment Manufacturer
  • OEM - Control Panelbuilder
  • Panel Builder
  • Electrician
  • System Integrator
  • IT Channel Partner
Carbon Footprint Of The Use Phase B2 B3 B4 B6
  • 0.1 kg CO2 eq.
  • 0.08962
Persona Type Ids
  • BM9
  • EU
  • LC
  • OM
  • OM8
  • PB
  • SC
  • SI
  • VR
Terminals Description ISO N 1
  • B
  • (33-34)NO_CL
  • (13-14-11-12)OF
Carbon Footprint Of The Distribution Phase A4
  • 0.0375419192
  • 0 kg CO2 eq.
Short Circuit Protection
  • 10 A fuse protection cartridge gG
Rated Operational Power In VA
  • 100 VA AC-15 1000000 cycles 60 cyc/mn 48 V 50/60 Hz 0.5 inductive
  • 450 VA AC-15 1000000 cycles 60 cyc/mn 127 V 50/60 Hz 0.5 inductive
  • 50 VA AC-15 1000000 cycles 60 cyc/mn 24 V 50/60 Hz 0.5 inductive
  • 750 VA AC-15 1000000 cycles 60 cyc/mn 230 V 50/60 Hz 0.5 inductive
Terminals Description ISO N 2
  • (43-44)NO_CL
  • (23-24-21-22)OF
  • B
Contact Code Designation
  • A300 AC-15, Ue = 240 V, Ie = 3 A IEC 60947-5-1 appendix A
  • Q300 DC-13, Ue = 250 V, Ie = 0.27 A IEC 60947-5-1 appendix A
Market Segmentation Id
  • COMMERCIAL
  • INDUSTRIAL
Shock Resistance
  • 100 gn IEC 60068-2-27
UIMP Rated Impulse Withstand Voltage
  • 6 kV IEC 60947-1



Compare