Altivar Machine ATV12 is an offer of variable speed drives for commercial equipment and simple machines. It works at a rated power up to 0.75kW / 1hp and a rated voltage from 200V to 240V AC. It is designed with heatsink for normal environments and fan-cooled enclosure. It has advanced PID and catch on the fly functions, basic cabling, and easy motor control setting. Based on the needs, it can be delivered without heatsink, with embedded EMC filter, or as standard version. The Altivar 12 drive integrates as standard the Modbus communication protocol. This Altivar Machine ATV12 is designed for simple applications, in industry, commercial machines and HVAC machines such as conveyors, pumps, extractors, access barriers and treadmills. It conforms to IEC, UL and other international standards. SoMove software compatibility enables saving and transfering of configurations to spare drive, reducing maintenance downtime. It features an optimized application of power and torque for ventilation and pumping applications, this allows up to 30% energy savings.

Technical Information

Applications
Asynchronous motors;Simple machine
Connection Type
1 RJ45
Connector Type
1 RJ45 (on front face) for Modbus
Enclosure
IP20
Mounting Type
Cabinet Mount
Net Weight
0.8 kg
Number of Phases
1 Phase
Output
230VAC 3-PHASE
Output Voltage
...240 V
Size
5.17 in
Standard
IEC 61800-3,IEC 61800-5-1,UL 508C,UL 618000-5-1
Storage Temperature
-25-70 degrees C
Type
Variable speed drive;Variable speed drive
Wattage
0.75 kW

Manufacturer Information

Brand
Schneider Electric
Sub Brand
ALTIVAR 12

General Product Info

12-Digit UPC
360648007107
Environmental Conditions
-10-40 A?C PROTECTIVE COVER FROM THE TOP OF THE DRIVE REMOVED-40-60 A?C WITH CURRENT DERATING 2.2 PER A?C
GTiN
03606480071072
Product UPC
78590169859
Weight
0.8 kg

Dimensions

Depth
5.16 in
Height
5.63 in
Warranty Length
18 mth
Width
2.83 in

Certifications and Compliance

CA Prop65 Warning
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Certifications
C-tick,CSA,GOST,KC,NOM,RCM,UL
Country of Origin
Indonesia
Environmental Class During Storage
  • class 1C3 according to IEC 60721-3-1
  • class 1S2 according to IEC 60721-3-1
US Rated Supply Voltage
  • 200...240 V - 15...10 %
CAD
  • https://download.schneider-electric.com/files?p_Doc_Ref=MCADID0000860_3D-CAD
  • https://download.schneider-electric.com/files?p_Doc_Ref=ATV12H075M2&p_File_name=ATV12H075M2.dwg
  • https://download.schneider-electric.com/files?p_Doc_Ref=ATV12H075M2&p_File_name
Continuous Output Current
  • 4.2 A 4 kHz
Prop 65
  • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Communication Service
  • read holding registers (03) 29 words
  • write single register (06) 29 words
  • write multiple registers (16) 27 words
  • read/write multiple registers
Related Products
  • VW3A4552
Method Of Access
  • server Modbus serial
Line Current
  • 10.2 A 100 V heavy duty)
  • 8.5 A 120 V heavy duty)
Motor Slip Compensation
  • preset in factory
  • adjustable
Frequency Resolution
  • analog input converter A/D, 10 bits
  • display unit 0.1 Hz
Protection Type
  • line supply overvoltage
  • line supply undervoltage
  • overcurrent between output phases and earth
  • overheating protection
  • short-circuit between motor phases
  • against input phase loss in three-phase
  • thermal motor protection via the drive by continuous calculatio
Accessories
  • VW3A9804
  • VW3A9523
Sampling Duration
  • 20 ms +/- 1 ms logic input
  • 10 ms analogue input
Linearity Error
  • +/- 0.3 % of maximum value analogue input
Environmental Class During Operation
  • class 3C3 according to IEC 60721-3-3
  • class 3S2 according to IEC 60721-3-3
Maximum Horse Power Rating
  • 1 hp
Time Constant
  • 20 ms +/- 1 ms for reference change
Vibration Resistance
  • 1 gn 13-200 Hz)IEC 60068-2-6
  • 1.5 mm peak to peak 3-13 Hz) - drive unmounted on symmetrical DIN rail - IEC 60068-2-6
  • 1.5 mm peak to peak 3-13 Hz) - drive unmounted on symmetrical DIN rail - IEC 600
Market Segmentation
  • Commercial
  • Industrial
Persona Type Names
  • Charge Point Operator
  • End User
  • Contractor
  • Original Equipment Manufacturer
  • OEM - Control Panelbuilder
  • Panel Builder
  • Electrician
  • IT Channel Partner
Electromagnetic Compatibility
  • electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
  • electros
Supply Frequency
  • 50/60 Hz +/- 5 %
Apparent Power
  • 2.0 kVA 240 V heavy duty)
Relative Humidity
  • 5-95 % without condensation IEC 60068-2-3
  • 5-95 % without dripping water IEC 60068-2-3
  • 5-95 % without dripping water IEC 60068-
Accessory Products
  • VW3A9804
  • VW3A9523
Persona Type Ids
  • BM9
  • EU
  • LC
  • OM
  • OM8
  • PB
  • SC
  • VR
Environmental Class During Transport
  • class 2C3 according to IEC 60721-3-2
  • class 2S1 according to IEC 60721-3-2
Electromagnetic Emission
  • radiated emissions environment 1 category C2 IEC 61800-3 2...16 kHz shielded motor cable
  • radiated emissions environment 1 category C2 IEC 61800-3 2...16 kHz shielded
Operating Altitude
  • > 3280.84...6561.68 ft (> 1000...2000 m) with current derating 1 % per 100 m
  • <= 3280.84 ft (1000 m) without derating
Asynchronous Motor Control Profile
  • quadratic voltage/frequency ratio
  • voltage/frequency ratio (V/f)
  • sensorless flux vector control
Transient Overtorque
  • 150-170 % of nominal motor torque depending on drive rating and type of motor
Market Segmentation Id
  • COMMERCIAL
  • INDUSTRIAL
Shock Resistance
  • 15 gn 11 ms IEC 60068-2-27
Maximum Transient Current
  • 6.3 A 60 s heavy duty)
  • 6.9 A 2 s heavy duty)
Power Dissipation In W
  • natural 44.0 W
Ambient Air Temperature For Operation
  • -10-40 °C without derating
  • 40-60 °C with current derating 2.2 % per °C
Switching Frequency
  • 2...16 kHz adjustable
  • 4...16 kHz with derating factor



Compare