Product image for SQD M9F15106 Miniature circuit brea

Email

SQD M9F15106 Miniature circuit brea

Manufacturer: Square-D / Schneider | Catalog # M9F15106 | Cooper Electric Part # 2009370

$187.50 /ea
ea
Log in or register to view your price, purchase history, and more!
Out of stock, please contact your sales representative for availability, pricing and lead times
This Multi9 C60H is a low voltage miniature circuit breaker (MCB). It is a 1P circuit breaker with 1 protected pole, 6A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 3kA at 415VAC conforming to EN/IEC 60947-2 st

Technical Information

Actuator
Toggle
Amperage
6 Amp 50 AmpC EN/IEC 60947-2
Applications
Provide interconnect and cross-connect of applications in entrance facilities, telecommunication rooms, data centers, at the desk and network applications to interconnect pre-terminated cassettes in main distribution, horizontal distribution, and equipment
Interrupt Rating
20 kAIC
Load Rating
7.5 KA 50 EN/IEC 60947-2 - 240 V AC 50/60 HZ-1.5 KA 50 EN/IEC 60947-2 - 415 V AC 50/60 HZ-20 KA 100 EN/IEC 60947-2 - <= 72 V DC
Number of Poles
1 Pole
Operating Temperature
-30 to 70 degrees C
TC Connection
Tunnel Terminal
Trip Type
Thermal Magnetic
Type
Miniature Push Button Box
Voltage
240 Volt AC 50/60 HZ BETWEEN PHASE AND NEUTRAL-415 Volt AC 50/60 HZ BETWEEN PHASE AND NEUTRAL-<= 72 Volt DC

Manufacturer Information

Brand
Schneider Electric
Sub Brand
C60H,MULTI 9 C60

General Product Info

12-Digit UPC
606480577508
Color
Gray
GTiN
03606480577505
Product UPC
60648057750

Dimensions

Depth
2.83 in
Height
81 mm
Length
72 mm
Width
0.7086 in
Heat Dissipation
  • 2.7-2.7 W 240 V - 6 A
Connections Terminals
  • tunnel type terminal top or bottom) 1-25 mm² - rigid
  • tunnel type terminal top or bottom) 1-25 m
Uimp Rated Impulse Withstand Voltage
  • 6 kVEN/IEC 60947-2
Carbon Footprint Of The Installation Phase A5
  • 0.005116018772296149
  • 0 kg CO2 eq.
Carbon Footprint Of The End Of Life Phase C1 To C4
  • 0.3 kg CO2 eq.
  • 0.31637386940174955
Ue Rated Operational Voltage
  • 240 V AC 50/60 Hz between phase and neutral
  • 415 V AC 50/60 Hz between phase and neutral
  • 415 V AC 50/60 Hz between phase an
Ui Rated Insulation Voltage
  • 500 V AC 50/60 Hz EN/IEC 60947-2
Ip Degree Of Protection
  • IP20 conforming to IEC 60529
  • IP40 (modular enclosure) conforming to IEC 60529
Carbon Footprint Of The Manufacturing Phase A1 To A3
  • 0.8 kg CO2 eq.
  • 0.759326917670991
Tropicalisation
  • 2 IEC 60068-1
Connection Pitch
  • 18 mm between devices
Ics Rated Service Breaking Capacity
  • 7.5 kA 50 % EN/IEC 60947-2 - 240 V AC 50/60 Hz
  • 7.5 kA 50 % EN/IEC
Carbon Footprint Of The Use Phase B2 B3 B4 B6
  • 6 kg CO2 eq.
  • 6.462923076923077
Line Rated Current
  • 6 A 50 °C EN/IEC 60947-2
Relative Humidity
  • 95-95 % 55-55 °C
Magnetic Tripping Limit
  • 12 x In +/- 20 % AC
  • 17 x In +/- 20 % DC
Wire Stripping Length
  • 14 mm for top or bottom connection
Carbon Footprint Of The Distribution Phase A4
  • 0.015766947497863417
  • 0 kg CO2 eq.
Tightening Torque
  • 2-2 N.m top or bottom
Network Type
  • DC
  • AC
Suitability For Isolation
  • yes EN/IEC 60947-2
Utilisation Category
  • category A EN/IEC 60947-2
Product Certifications
  • EAC
  • CCC



Compare