TeSys GV motor circuit breaker, 3 poles (3P), 115A/690V, for protection of 3-phase motors 37-55kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 25kA@400V, start-stop control by rotary handle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 65-115A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX).

Technical Information

Line Rated Current
115 A
Net Weight
1.6 kg
Standard
CSA C22.2 No 60947-4-1,EN/IEC 60947-2,EN/IEC 60947-4-1,UL 60947-4-1
Storage Temperature
-50-85 degrees C
Trip Point
1955-1955 A

Manufacturer Information

Brand
Schneider Electric

General Product Info

12-Digit UPC
360648131017
Color
Gray
GTiN
03606481310149
Product UPC
60648131014
Weight
1.6 kg

Dimensions

Depth
165 mm
Height
6.1 in
Warranty Length
18 mth
Width
3.19 in

Certifications and Compliance

CA Prop65 Warning
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Certifications
ATEX,CCC,CSA,EAC,EU-RO MR,IEC,UL
Country of Origin
Poland
Features
  • New modern look & feel of all machines
  • Wide range of GVs: Magnetic, thermal magnetic, different sizes (GV2,GV3,GV4)
  • Easier to install and operate with multi-standard screws
  • Sturdy and long-lasting power connection with EverLink terminals
  • Digital customer experience for technical documents
  • Maintenance guide via EcoStruxureTM Facility Expect
Prop 65
  • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Accessory Products
  • LV429375
Related Products
  • LC1D115F7
  • LC1D115P7
  • LC1D115B7
  • LC1D115BD
  • LC1D115FD



Compare