SQUARED LC2D150BD TeSys Deca revers

Manufacturer: Square-D / Schneider | Catalog # LC2D150BD | Cooper Electric Part # 1926392

$5,061.43 /ea
ea
Log in or register to view your price, purchase history, and more!
Out of stock, please contact your sales representative for availability, pricing and lead times
TeSys Deca reversing contactor, 3 poles (3NO), for motor control applications up to 150A/1000V AC-3 (75kW@400V). Rated 150A AC-3 75kW@400V, it includes a 24V DC coil, 2NO+2NC aux contacts, mechanical and electrical interlock. It provides 24V DC coils with transient suppressor module, 2NO+2NC built-in auxiliary contacts (NC mirrror certified), power connection by screw connectors 2 inputs, control by screw clamp terminals. For operating rates until 1200 cycles/hour and environments until 60.C, it procures high reliability and durability. Compact (266mm width), mounting on 2 DIN-rails or screw fixing. With pre-wired reversing power connections, mechanical and electrical interlock. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). Assembled with mechanical and electrical interlock and pre-wired reversing circuit. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections. Equipped with a 24V DC coil for easy integration to all control systems. Provides 4 built-in auxiliary contacts 2NO + 2NC, NC contacts are mirror certified suitable to be included in the control of safety systems. High electrical durability, guaranteed for 0.8 million cycles at 150A AC-3 440V, for demanding motor switching applications. Robust design with high making and breaking capacities up to 20 In. Connection by screw clamp terminals.

Technical Information

Amperage
200 Amp 60C 440 VAC VAC-1 POWER CIRCUIT-150 Amp 60C 440 VAC VAC-3 POWER CIRCUIT
Applications
Exterior Lighting, Interior Lighting, Security Lighting, Parking Lot Lighting, Bell Ringing, Electric Motors, Electric Pump, Indoor
Coil Voltage
24 V DC,24 V DC STANDARD,POWER CIRCUIT <= 1000 V AC 25...400 HZ-POWER CIRCUIT <= 300 V DC
Contact Configuration
15amp/120-277vac
Contact Rating
200 A 60 AC POWER CIRCUIT
Impedance
0.6 MOhm - Ith 200 A 50 Hz For Power Circuit
Net Weight
6.4 kg
Operating Cycles
1200 CYC/H 60 AC,25...400 HZ
Operating Temperature
-40 to 70 degrees C, -5 to 60 degrees C
Range
TeSys
Size
148 MM,158 MM,266 MM
Standard
CSA C22.2 No 14,EN 60947-4-1,EN 60947-5-1,IEC 60947-4-1,IEC 60947-5-1,UL 508
Storage Temperature
-60-80 degrees C
TC Connection
CONTROL CIRCUIT SCREW CLAMP TERMINALS 2 1-2.5 MMAFLEXIBLE WITH CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 1 1-2.5 MMAFLEXIBLE WITHOUT CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 2 1-2.5 MMAFLEXIBLE WITHOUT CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 1 1-2.5 MMAFLEXIBLE WITH CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 1 1-2.5 MMASOLID WITHOUT CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 2 1-2.5 MMASOLID WITHOUT CABLE END-POWER CIRCUIT CONNECTOR 1 10-120 MMAFLEXIBLE WITHOUT CABLE END-POWER CIRCUIT CONNECTOR 2 10-50 MMAFLEXIBLE WITHOUT CABLE END-POWER CIRCUIT CONNECTOR 1 10-120 MMAFLEXIBLE WITH CABLE END-POWER CIRCUIT CONNECTOR 2 10-50 MMAFLEXIBLE WITH CABLE END-POWER CIRCUIT CONNECTOR 1 10-120 MMASOLID WITHOUT CABLE END-POWER CIRCUIT CONNECTOR 2 10-50 MMASOLID WITHOUT CABLE END
Type
MECHANICAL-ELECTRICAL,REVERSING CONTACTOR,REVERSING CONTACTOR
Wattage
24 Watt AC-1 - 13.5 Watt AC-3

Manufacturer Information

Brand
Schneider Electric
Sub Brand
TESYS D

General Product Info

12-Digit UPC
389118074982
GTiN
03389118074989
Product UPC
78590182613
Weight
6.4 kg

Dimensions

Depth
5.83 in
Height
6.22 in
Warranty Length
18 mth
Width
10.47 in

Certifications and Compliance

CA Prop65 Warning
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Certifications
BV,CCC,CSA,DNV,EAC,GL,RINA,UKCA,UL
Country of Origin
Czechia
Insulation Resistance
  • > 10 MOhm for signalling circuit
Power Range
  • 30-50 kW 200-240 V 3 phase
  • 55-100 kW 380-440 V 3 phase
  • 55-100 kW 480-500 V 3 phase
Connections Terminals
  • control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end
  • control circuit screw clamp terminals 1 1-2.5 mm²flexible without cable end
  • control circuit screw clamp terminals 2 1-2.5 mm²flexible without cable end
  • control circuit screw clamp terminals 1 1-2.5 mm²flexible with cable end
  • control circuit screw clamp terminals 1 1-2.5 mm²solid without cable end
  • control circuit screw clamp terminals 2 1-2.5 mm²solid without cable end
  • power circuit connector 1 10-120 mm²flexible without cable end
  • power circuit connector 2 10-50 mm²flexible without cable end
  • power circuit connector 1 10-120 mm²flexible with cable end
  • power circuit connector 2 10-50 mm²flexible with cable end
  • power circuit connector 1 10-120 mm²solid without cable end
  • power circuit connector 2 10-50 mm²solid without cable end
IE Rated Operational Current
  • 200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
  • 150 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
ITH Conventional Free Air Thermal Current
  • 200 A (at 60 °C) for power circuit
IP Degree Of Protection
  • IP20 front face IEC 60529
Power Dissipation Per Pole
  • 24 W AC-1
  • 13.5 W AC-3
Maximum Operating Rate
  • 1200 cyc/h 60 °C
Prop 65
  • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Carbon Footprint Of The Installation Phase A5
  • 0.6795334937194923
  • 0.7 kg CO2 eq.
Non Overlap Time
  • 1.5 ms on de-energisation between NC and NO contact
  • 1.5 ms on energisation between NC and NO contact
Carbon Footprint Of The End Of Life Phase C1 To C4
  • 11 kg CO2 eq.
  • 11.330063403179329
Standards
  • CSA C22.2 No 14
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60947-4-1
  • IEC 60947-5-1
  • UL 508
Operating Time
  • 20...35 ms closing
  • 40...75 ms opening
Control Circuit Type
  • DC standard
Minimum Switching Voltage
  • 17 V for signalling circuit
UC Control Circuit Voltage
  • 24 V DC
ICW Rated Short Time Withstand Current
  • 250 A 40 °C - 10 min for power circuit
  • 580 A 40 °C - 1 min for power circuit
  • 1200 A 40 °C - 10 s for power circuit
  • 1400 A 40 °C - 1 s for power circuit
  • 100 A - 1 s for signalling circuit
  • 120 A - 500 ms for signalling circuit
  • 140 A - 100 ms for signalling circuit
Related Products
  • with
Carbon Footprint Of The Manufacturing Phase A1 To A3
  • 57 kg CO2 eq.
  • 56.905760411244486
Protective Treatment
  • TH IEC 60068-2-30
UI Rated Insulation Voltage
  • power circuit 600 V CSA
  • power circuit 600 V UL
  • signalling circuit 690 V IEC 60947-1
  • signalling circuit 600 V CSA
  • signalling circuit 600 V UL
  • power circuit 1000 V IEC 60947-4-1
Average Impedance
  • 0.6 mOhm - Ith 200 A 50 Hz for power circuit
Contactor Coil Voltage
  • 24 V DC standard
Electrical Durability
  • 0.85 Mcycles 150 A AC-3 <= 440 V
  • 1 Mcycles 200 A AC-1 <= 440 V
Maximum Horse Power Rating
  • 40 hp at 200/208 V AC 60 Hz for 3 phase motors
  • 50 hp at 230/240 V AC 60 Hz for 3 phase motors
  • 100 hp at 460/480 V AC 60 Hz for 3 phase motors
  • 125 hp at 575/600 V AC 60 Hz for 3 phase motors
Market Segmentation
  • Commercial
  • Industrial
Persona Type Names
  • End User
  • Original Equipment Manufacturer
  • OEM - Control Panelbuilder
  • Panel Builder
Inrush Power In W
  • 270-365 W 20 °C
Fire Resistance
  • 850 °C IEC 60695-2-1
Contactor Application
  • motor control
  • resistive load
Motor Power KW
  • 40 kW at 220...230 V AC 50 Hz
  • 75 kW at 380...400 V AC 50 Hz
  • 80 kW at 415...440 V AC 50 Hz
  • 90 kW at 500 V AC 50 Hz
  • 100 kW at 660...690 V AC 50 Hz
  • 75 kW at 1000 V AC 50 Hz
Flame Retardance
  • V1 conforming to UL 94
Carbon Footprint Of The Use Phase B2 B3 B4 B6
  • 178 kg CO2 eq.
  • 178.22012589928053
Persona Type Ids
  • EU
  • OM
  • OM8
  • PB
Safety Reliability Level
  • B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Carbon Footprint Of The Distribution Phase A4
  • 1.9222858853720504
  • 2 kg CO2 eq.
Tightening Torque
  • control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm
  • control circuit 1.2 N.m screw clamp terminals Philips No 2
  • power circuit 12 N.m connector hexagonal 4 mm
  • control circuit 1.2 N.m screw clamp terminals pozidriv No 2
Mechanical Robustness
  • vibrations contactor open2 Gn, 5...300 Hz
  • vibrations contactor closed4 Gn, 5...300 Hz
  • shocks contactor closed15 Gn for 11 ms
  • shocks contactor open6 Gn for 11 ms
Interlocking Type
  • mechanical
  • electrical
Minimum Switching Current
  • 5 mA for signalling circuit
Control Circuit Voltage Limits
  • 0.15...0.4 Uc (-40-70 °C):drop-out DC
  • 0.75...1.2 Uc (-40-55 °C):operational DC
  • 1...1.2 Uc (55-70 °C):operational DC
Hold In Power Consumption In W
  • 2.4-5.1 W 20 °C
Market Segmentation Id
  • COMMERCIAL
  • INDUSTRIAL
IRMS Rated Making Capacity
  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
  • 1660 A at 440 V for power circuit conforming to IEC 60947
Associated Fuse Rating
  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
  • 315 A gG at <= 690 V coordination type 1 for power circuit
  • 250 A gG at <= 690 V coordination type 2 for power circuit
Ambient Air Temperature For Operation
  • -40-60 °C
  • 60-70 °C with derating
UE Rated Operational Voltage
  • power circuit <= 1000 V AC 25...400 Hz
  • power circuit <= 300 V DC
Rated Breaking Capacity
  • 1400 A at 440 V for power circuit conforming to IEC 60947
Product Certifications
  • BV
  • CCC
  • CSA
  • DNV
  • GL
  • RINA
  • UL
  • EAC
  • UKCA
UIMP Rated Impulse Withstand Voltage
  • 8 kV IEC 60947



Compare