Product image for SolaHD 63-23-230-8 3000 VA 480 Volt Input 120/240 Volt Output 1-Phase Constant Voltage Power Conditioner
Image thumbnail 0
Image thumbnail 1

Email

SolaHD 63-23-230-8 3000 VA 480 Volt Input 120/240 Volt Output 1-Phase Constant Voltage Power Conditioner

Manufacturer: Sola Electric | Catalog # 63-23-230-8 | Cooper Electric Part # 173409

$4,378.15/ea
ea
Log in or register to view your price, purchase history, and more!
Out of stock, please contact your sales representative for availability, pricing and lead times
MCR Hardwired Series Power Line Conditioning with Voltage Regulation provides excellent noise filtering and surge protection to safeguard connected equipment against damage, degradation or malfunction. This protection, combined with the excellent voltage regulation, can significantly increase the MTBF of protected equipment. The MCR is a perfect choice where dirty power caused by impulses, swell, sags, brownouts or waveform distortion can lead to costly downtime due to damaged equipment.

Technical Information

Amperage
7500 VA
Applications
Industrial Automation and Control Equipment Power PLCs, Broadcast Equipment, Photo Processing Equipment
Efficiency
Up to 92% at Full Load PCT
Max Output Power
120/208/240
Number of Phases
1 Phase
Operating Temperature
-20 to 50 degrees C
Primary Voltage
240/480 VAC
Secondary Voltage
120/240 VAC
Size
27 High x 25 Wide x 9 Deep IN
Style
1
Type
CVS Hardwired Series - Constant Voltage Transformers

Manufacturer Information

Brand
SolaHD

General Product Info

12-Digit UPC
783472221752
GTiN
00783472221752
Product UPC
78347222175

Dimensions

Height
19 Inch
Length
9 Inch
Width
13 in

Certifications and Compliance

Buy American Compliant
Y
Features
  • cULus, CSA, RoHS
  • 3% output voltage regulation
  • Noise attenuation: 120 dB in common mode and 60 dB in transverse mode
  • Surge protection tested to ANSI/IEEE C62.41 Class A & B Waveform: <10 V let through typical
  • Acts as a step-up or step-down transformer
  • Harmonic filtering
  • Hardwired
  • Galvanic isolation provides exceptional circuit protection
  • 25 year typical MTBF. No maintenance required



Compare