variable speed drive, Altivar Process ATV900, ATV950, 7.5kW, 10hp, 380 to 480V, IP55, UL type12, disconnect switch

Technical Information

Accuracy
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 C analog input;+/- 1 % AQ1, AQ2 for a temperature variation 60 C analog output
Applications
Asynchronous motors;synchronous motors;Process for industrial;Industrial Application
Connection Type
1 RJ45,2 RJ45
Connector Type
2 RJ45 for Ethernet IP/Modbus TCP on the control block;1 RJ45 for Modbus serial on the control block
Input Voltage
380...480 V - 15...10 %
Mounting Type
Wall-Mounted
Net Weight
13.7 kg
Number of Phases
3 Phase
Output Voltage
<= power supply voltage
Size
12.99 in
Standard
IEC 13849-1,IEC 60721-3,IEC 61000-3-12,IEC 61508,IEC 61800-3,IEC 61800-5-1,UL 508C
Storage Temperature
-40-70 degrees C
Type
Variable speed drive;2 RJ45;1 RJ45

Manufacturer Information

Brand
Schneider Electric
Sub Brand
ATV950

General Product Info

12-Digit UPC
785901067061
GTiN
03606481284433
Product UPC
78590106706
Weight
13.7 kg

Dimensions

Depth
12.99 in
Height
26.69 in
Width
10.39 in

Certifications and Compliance

CA Prop65 Warning
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Certifications
ABS,ATEX INERIS,Bureau Veritas,CSA,DNV-GL,TV,UL
Country of Origin
China
Environmental Class During Storage
  • class 1C3 according to EN 60721-3-1
  • class 1S2 according to EN 60721-3-1
US Rated Supply Voltage
  • 380...480 V - 15...10 %
Exchange Mode
  • half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
Type Of Polarization
  • no impedance Modbus serial
Analogue Input Type
  • AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits
  • AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits
Continuous Output Current
  • 16.5 A 4 kHz normal duty
  • 12.7 A 4 kHz heavy duty
Prop 65
  • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Analogue Output Type
  • software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits
  • software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
Carbon Footprint Of The Installation Phase A5
  • 8 kg CO2 eq.
  • 8.4315922671
Carbon Footprint Of The End Of Life Phase C1 To C4
  • 3.4514551845
  • 3 kg CO2 eq.
Encoder Protocol
  • 1 Vpp
  • EnDat 2.2
  • resolver
  • RS 422
  • SSI 24V
  • SSI 5V
  • TTL/HTL
Discrete Input Type
  • DI1...DI8 programmable, 24 V DC <= 30 V)3.5 kOhm
  • DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
  • STOA, STOB safe torque off, 24 V DC <= 30 V)> 2.2 kOhm
Electrical Connection
  • control screw terminal 0.5...1.5 mm²
  • motor screw terminal 6...10 mm²
  • line side screw terminal 4...6 mm²
  • DC bus screw terminal 4...10 mm²
Carbon Footprint Of The Manufacturing Phase A1 To A3
  • 213 kg CO2 eq.
  • 213.022056239
Method Of Access
  • slave Modbus TCP
Line Current
  • 13.8 A 380 V normal duty)
  • 10.5 A 380 V heavy duty)
  • 11.9 A 480 V normal duty)
  • 9.2 A 480 V heavy duty)
Motor Slip Compensation
  • adjustable
  • can be suppressed
  • not available in permanent magnet motor law
  • automatic whatever the load
Variant
  • with braking chopper
  • with load break switch
Maximum Switching Current
  • relay output R1 resistive, cos phi = 1 3 A 250 V AC
  • relay output R1 resistive, cos phi = 1 3 A 30 V DC
  • relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC
  • relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC
  • relay output R2, R3 resistive, cos phi = 1 5 A 250 V AC
  • relay output R2, R3 resistive, cos phi = 1 5 A 30 V DC
  • relay output R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC
  • relay output R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC
Relay Output Type
  • configurable relay logic R1 fault relay NO/NC 100000 cycles
  • configurable relay logic R2 sequence relay NO 1000000 cycles
  • configurable relay logic R3 sequence relay NO 1000000 cycles
Input Compatibility
  • DI1...DI8 discrete input level 1 PLC IEC 61131-2
  • DI7, DI8 pulse input level 1 PLC IEC 65A-68
  • STOA, STOB discrete input level 1 PLC IEC 61131-2
Protection Type
  • thermal protection motor
  • safe torque off motor
  • motor phase break motor
  • thermal protection drive
  • safe torque off drive
  • overheating drive
  • overcurrent between output phases and earth drive
  • overload of output voltage drive
  • short-circuit protection drive
  • motor phase break drive
  • overvoltages on the DC bus drive
  • line supply overvoltage drive
  • line supply undervoltage drive
  • line supply phase loss drive
  • overspeed drive
  • break on the control circuit drive
Sampling Duration
  • 2 ms +/- 0.5 ms DI1...DI8) - discrete input
  • 5 ms +/- 1 ms DI7, DI8) - pulse input
  • 1 ms +/- 1 ms AI1, AI2, AI3) - analog input
  • 5 ms +/- 1 ms AQ1, AQ2) - analog output
Linearity Error
  • AI1, AI2, AI3 +/- 0.15 % of maximum value analog input
  • AQ1, AQ2 +/- 0.2 % analog output
Environmental Class During Operation
  • class 3C3 according to IEC 60721-3-3
  • class 3S3 according to IEC 60721-3-3
Persona Type Names
  • End User
  • Original Equipment Manufacturer
  • OEM - Control Panelbuilder
  • System Integrator
Motor Power KW
  • 7.5 kW normal duty
  • 5.5 kW heavy duty
Refresh Time
  • relay output R1, R2, R3)5 ms +/- 0.5 ms)
Carbon Footprint Of The Use Phase B2 B3 B4 B6
  • 7 916 kg CO2 eq.
  • 7916.4894184123
Electromagnetic Compatibility
  • electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
  • radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
  • electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
  • 1.2/50 s - 8/20 s surge immunity test level 3 conforming to IEC 61000-4-5
  • conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Apparent Power
  • 9.9 kVA 480 V normal duty)
  • 7.6 kVA 480 V heavy duty)
Persona Type Ids
  • EU
  • OM
  • OM8
  • SI
Environmental Class During Transport
  • class 2C3 according to EN 60721-3-2
  • class 2S1 according to EN 60721-3-2
Number Of Addresses
  • 1-247 Modbus serial
Maximum THDI
  • <48 % from 80...100 % of load IEC 61000-3-12
Carbon Footprint Of The Distribution Phase A4
  • 3.3777091388
  • 3 kg CO2 eq.
Synchronous Motor Control Profile
  • permanent magnet motor
  • synchronous reluctance motor
Minimum Switching Current
  • relay output R1, R2, R3 5 mA 24 V DC
Operating Altitude
  • <= 3280.84 ft (1000 m) without derating
  • 1000...4800 m with current derating 1 % per 100 m
Noise Level
  • 52 dB 86/188/EEC
Asynchronous Motor Control Profile
  • variable torque standard
  • constant torque standard
  • optimized torque mode
Discrete Output Type
  • logic output DQ+ 0-1 kHz <= 30 V DC 100 mA
  • programmable as pulse output DQ+ 0-30 kHz <= 30 V DC 20 mA
  • logic output DQ- 0-1 kHz <= 30 V DC 100 mA
Maximum Transient Current
  • 19.8 A 60 s normal duty)
  • 19.1 A 60 s heavy duty)
Transmission Rate
  • 10/100 Mbit/s Ethernet IP/Modbus TCP
  • 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial
Ambient Air Temperature For Operation
  • -15-40 °C (without derating)
  • 40-50 °C (with derating factor)
UE Rated Operational Voltage
  • 380...480 V 7.5 kW normal duty
  • 380...480 V 5.5 kW heavy duty
Data Format
  • 8 bits, configurable odd, even or no parity Modbus serial
Switching Frequency
  • 2...16 kHz adjustable
  • 4...16 kHz with derating factor



Compare