Product image for SQD 28905 NON-AUTOMATIC SWITCH INTE

Email

SQD 28905 NON-AUTOMATIC SWITCH INTE

Manufacturer: Square-D / Schneider | Catalog # 28905 | Cooper Electric Part # 1535745

$393.00 /ea
ea
Log in or register to view your price, purchase history, and more!
Out of stock, please contact your sales representative for availability, pricing and lead times
This Compact INS80 is a 4 poles non-automatic switch-disconnector with black rotary handle. It is suitable for isolation with positive contact indication, as defined by IEC 60947-1 and IEC60947-3 standards. The operational current is 80A at 415VAC in cat

Technical Information

Actuator
ROTARY HANDLE
Amperage
AC-23A 40 Amp AC 50/60 HZ 500 V-DC-23A 80 Amp DC 125 V 2 POLES IN SERIES-DC-22A 80 Amp DC 250 V 4 POLES IN SERIES-DC-23A 80 Amp DC 250 V 4 POLES IN SERIES-AC-23A 63 Amp AC 50/60 HZ 440/480 V-AC-22A 80 Amp AC 50/60 HZ 220/240 V-AC-22A 80 Amp AC 50/60 HZ 380/415 V-AC-22A 80 Amp AC 50/60 HZ 440/480 V-AC-22A 80 Amp AC 50/60 HZ 500 V-AC-23A 72 Amp AC 50/60 HZ 380/415 V-AC-23A 80 Amp AC 50/60 HZ 220/240 V-DC-22A 80 Amp DC 125 V 2 POLES IN SERIES
Applications
INS40...160
Mounting Type
Fixed
Net Weight
0.6 kg
Number of Poles
4 Pole
Operating Temperature
-25-70 Adegrees C
Standard
IEC 60947-1,IEC 60947-3
Storage Temperature
-50-85 degrees C
Type
SWITCH DISCONNECTOR
Voltage
500 Volt AC 50/60 HZ-250 Volt DC

Manufacturer Information

Brand
Schneider Electric
Sub Brand
COMPACT INS,COMPACT INS80,COMPACT INS80

General Product Info

12-Digit UPC
303430289053
GTiN
03303430289050
Handle Color
Black
Product UPC
78590155152
Weight
0.6 kg

Dimensions

Depth
2.46 in
Height
3.35 in
Length
62.5 mm
Warranty Length
18 mth
Width
3.54 in

Certifications and Compliance

CA Prop65 Warning
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go t
Certifications
CCC,KEMA-KEUR
Country of Origin
USA
Mounting Support
  • plate
  • DIN rail
Prop 65
  • WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go t
Carbon Footprint Of The Installation Phase A5
  • 0.0316395703007111
  • 0 kg CO2 eq.
Carbon Footprint Of The End Of Life Phase C1 To C4
  • 1 kg CO2 eq.
  • 1.0630700960039061
Standards
  • IEC 60947-3
  • IEC 60947-1
Ue Rated Operational Voltage
  • 500 V AC 50/60 Hz
  • 250 V DC
Ui Rated Insulation Voltage
  • 690 V AC 50/60 Hz
Icm Rated Short Circuit Making Capacity
  • 15 kA switch-disconnector alone 500 V AC 50/60 Hz
  • 75 k
Ip Degree Of Protection
  • IP40 conforming to IEC 60529
Carbon Footprint Of The Manufacturing Phase A1 To A3
  • 4 kg CO2 eq.
  • 4.088403222631061
Electrical Durability
  • AC-22A 1500 cycles 220/240 V AC 50/60 Hz
  • AC-22A 1500 cycles 380/415 V AC 50/60 Hz
  • AC-22A 1
Carbon Footprint Of The Use Phase B2 B3 B4 B6
  • 87 kg CO2 eq.
  • 87.17537623125291
Carbon Footprint Of The Distribution Phase A4
  • 0.09077644459286428
  • 0.1 kg CO2 eq.
Ith Conventional Free Air Thermal Current
  • 80 A 60 °C
Network Type
  • AC
  • DC
Ie Rated Operational Current
  • AC-23A 40 A AC 50/60 Hz 500 V
  • AC-23A 63 A AC 50/60 Hz 440/480 V
  • AC
Icw Rated Short Time Withstand Current
  • 0.67 kA 20 s IEC 60947-3
  • 1.73 kA 3 s IEC 60947-3
  • 3 kA 1 s IEC 60947-3
  • 0.55 kA 30 s IEC 60947-3
  • 0.55 kA 30 s IEC 60
Maximum Power
  • AC-23 22 kW 500/525 V AC 50/60 Hz
  • AC-23 22 kW 220/240 V AC 50/60 Hz
  • AC-23 22 kW 220/
Product Certifications
  • CCC
  • KEMA-KEUR



Compare