Applications
Motor control;Resistive load
Coil Voltage
24 V DC,24 V DC STANDARD,POWER CIRCUIT <= 690 V AC 25...400 HZ-POWER CIRCUIT <= 300 V DC
Contact Configuration
1 NO + 1 NC,3 NO
Contact Rating
10 A 60 AC SIGNALLING CIRCUIT-40 A 60 AC POWER CIRCUIT
Impedance
2 MOhm - Ith 40 A 50 Hz For Power Circuit
Operating Cycles
3600 cyc/h 60 C
Operating Temperature
-40-70 Adegrees C AT UC,-5-60 Adegrees C
Standard
CSA C22.2 No 14,EN 60947-4-1,EN 60947-5-1,IEC 60335-1,IEC 60947-4-1,IEC 60947-5-1,UL 508
Storage Temperature
-60-80 degrees C
TC Connection
CONTROL CIRCUIT SCREW CLAMP TERMINALS 1 1-4 MMAFLEXIBLE WITHOUT CABLE END-POWER CIRCUIT SCREW CLAMP TERMINALS 2 1.5-6 MMAFLEXIBLE WITH CABLE END-POWER CIRCUIT SCREW CLAMP TERMINALS 1 1.5-10 MMASOLID WITHOUT CABLE END-POWER CIRCUIT SCREW CLAMP TERMINALS 2 2.5-10 MMASOLID WITHOUT CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 2 1-4 MMAFLEXIBLE WITHOUT CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 1 1-4 MMAFLEXIBLE WITH CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 2 1-2.5 MMAFLEXIBLE WITH CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 1 1-4 MMASOLID WITHOUT CABLE END-CONTROL CIRCUIT SCREW CLAMP TERMINALS 2 1-4 MMASOLID WITHOUT CABLE END-POWER CIRCUIT SCREW CLAMP TERMINALS 1 2.5-10 MMAFLEXIBLE WITHOUT CABLE END-POWER CIRCUIT SCREW CLAMP TERMINALS 2 2.5-10 MMAFLEXIBLE WITHOUT CABLE END-POWER CIRCUIT SCREW CLAMP TERMINALS 1 1-10 MMAFLEXIBLE WITH CABLE END
Wattage
3.2 Watt AC-1 - 1.25 Watt AC-3
CA Prop65 Warning
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Certifications
BV,CB,CCC,CSA,DNV,GL,GOST,LROS (Lloyds Register Of Shipping),RINA,UKCA,UL
Country of Origin
Indonesia