XAL control stations are suitable for most common functions. This control station has three 22mm push buttons. One flush black push button operator has a normally open contact and is marked UP. One flush black push button operator has a normally open contact and is marked DOWN. One flush red push button has a normally closed contact and is marked STOP. Contacts have UL A600, UL Q600, IEC AC15 and IEC DC13 contact ratings. Enclosure has knockouts for wire entry. Control Station is 5.35 inches tall, 2.68 inches wide and 2.44 inches deep. The relay weighs 0.66 lbs. Control station is UL Listed and CSA certified. "This product meets EN/IEC 60947-5-4, EN/IEC 60947-1, EN/IEC 60947-5-5 and EN/IEC 60947-5-1 standards." "This range of control stations combines simplicity of setup with compact size and flexibility. It is ideal for applications requiring good resistance to chemical agents." "Plastic XALD/XALK control stations and enclosures for . 22mm plastic pushbuttons (XB5/ZB5 range)."

Technical Information

Amperage
6 Amp 120 V, AC-15, A600 EN/IEC 60947-5-1-3 Amp 240 V, AC-15, A600 EN/IEC 60947-5-1-1.2 Amp 600 V, AC-15, A600 EN/IEC 60947-5-1-0.55 Amp 125 V, DC-13, Q600 EN/IEC 60947-5-1-0.27 Amp 250 V, DC-13, Q600 EN/IEC 60947-5-1-0.1 Amp 600 V, DC-13, Q600 EN/IEC 60947-5-1
Applications
Three functions;For XB5 22 mm control and signalling units
Cable Entry
14-14 mm
Contact Material
Silver Alloy
Enclosure
NEMA 13-NEMA 4X
Material
Polycarbonate
Net Weight
0.299 kg
Operating Temperature
-40-70 Adegrees C
Standard
IEC 60947-1,IEC 60947-5-1,IEC 60947-5-4,IEC 60947-5-5
Storage Temperature
-40-70 degrees C
TC Connection
SCREW CLAMP TERMINALS, <= 2 X 1.5 MMA WITH CABLE END EN/IEC 60947-1-SCREW CLAMP TERMINALS, >= 1 X 0.22 MMA WITHOUT CABLE END EN/IEC 60947-1
Type
Complete control station

Manufacturer Information

Brand
Schneider Electric
Sub Brand
XALD

General Product Info

12-Digit UPC
389119044656
GTiN
03389119044653
Product UPC
78590157921
Weight
0.299 kg

Dimensions

Warranty Length
18 mth

Certifications and Compliance

CA Prop65 Warning
This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
Country of Origin
France
Connections Terminals
  • screw clamp terminals, <= 2 x 1.5 mm² with cable end IEC 60947-1
  • screw clamp terminals, <= 2 x 1.5 mm² with cable end IEC 60
Color Of Base Of Enclosure
  • light grey RAL 7035)
IE Rated Operational Current
  • 6 A 120 V, AC-15, A600 IEC 60947-5-1
  • 3 A 240 V, AC-15, A600 IEC 60947-5-1
  • 3 A 240 V, AC-15, A600 IEC 60947
ITH Conventional Free Air Thermal Current
  • 10 A IEC 60947-5-1
IP Degree Of Protection
  • IP66 IEC 60529
  • IP69
  • IP69K
  • IP67
Shape Of Screw Head
  • cross Philips no 1
  • cross pozidriv No 1
  • slotted flat Ø 4 mm
  • slotted flat Ø 5.5 mm
Carbon Footprint Of The Installation Phase A5
  • 0.0012529230187181394
  • 0 kg CO2 eq.
Carbon Footprint Of The End Of Life Phase C1 To C4
  • 0.6 kg CO2 eq.
  • 0.6226672987015506
Cable Entry
  • 2 knock-outs for cable entry 14-14 mm
  • 2 knock-outs for Pg 13 cable gland and ISO M20 12-12 mm
Carbon Footprint Of The Manufacturing Phase A1 To A3
  • 2 kg CO2 eq.
  • 1.5831899241373928
Electrical Shock Protection Class
  • class II conforming to IEC 60536
Nema Degree Of Protection
  • NEMA 13
  • NEMA 4X
UI Rated Insulation Voltage
  • 600 V 3)IEC 60947-1
Electrical Durability
  • 1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C
  • 1000000 cycles, AC-15, 2 A 230 V 36
Vibration Resistance
  • 5 gn (f= 12-500 Hz) conforming to IEC 60068-2-6
Market Segmentation
  • Commercial
  • Industrial
Color Of Cover
  • dark grey RAL 7016)
Persona Type Names
  • Charge Point Operator
  • End User
  • Contractor
  • Original Equipment Manufacturer
  • OEM - Control Panelbuilder
  • Panel Builder
  • Electrician
  • System Integrator
  • IT Channel Partner
Carbon Footprint Of The Use Phase B2 B3 B4 B6
  • 0 kg CO2 eq.
  • 0
Persona Type Ids
  • BM9
  • EU
  • LC
  • OM
  • OM8
  • PB
  • SC
  • SI
  • VR
Carbon Footprint Of The Distribution Phase A4
  • 0.21257263933090792
  • 0.2 kg CO2 eq.
Tightening Torque
  • 0.8-1.2 N.m IEC 60947-1
Resistance To High Pressure Washer
  • 7000000 Pa 55 °C 0.1 m
Short Circuit Protection
  • 10 A cartridge fuse gG IEC 60947-5-1
Market Segmentation Id
  • COMMERCIAL
  • INDUSTRIAL
Electrical Reliability
  • ? < 10exp(-6) 5 V 1 mA IEC 60947-5-4
  • ? < 10exp(-8) 17 V 5 mA IEC 60947-5-4
  • ? < 10exp(-8) 17 V 5 mA IEC 60
Shock Resistance
  • 30 gn 18 ms) half sine wave acceleration IEC 60068-2-27
  • 50 gn 11 ms) half sine wave ac
UIMP Rated Impulse Withstand Voltage
  • 6 kV IEC 60947-1