A Three-Phase Power Logger (EU and US) built with Fluke Connect mobile app and desktop software compatibility to give you the data you need to make critical power quality and energy decisions in real-time. The ideal test tools for conducting energy studies and basic power quality logging, it automatically captures and logs over 500 power quality parameters so you have more visibility into the data you need to optimize system reliability and savings.

Technical Information

Applications
Automatically capture and log voltage, current, power, harmonics and associated power quality values.
Operating Temperature
-10 To 50 degrees C
Storage Temperature
-20 To 50 degrees C
Type
Energy Logger

Manufacturer Information

Brand
Fluke Corporation
Sub Brand
Fluke

General Product Info

12-Digit UPC
095969758499
GTiN
00095969758499
Product UPC
09596975849
Weight
0.9 lb

Dimensions

Warranty Length
1 yr
Features
  • Versatile, three-phase power loggers for conducting energy, load and power quality studies.
  • Automatically capture and log voltage, current, power, harmonics and associated power quality values, and capture dips, swells, and inrush currents with event waveform snapshots and high-resolution RMS profiles.
  • Convenient instrument powering
  • directly from the measured circuit
  • Download and analyze every detail of energy consumption and power quality state of health with our automated reporting.
Current Inputs
  • Number of inputs: 4, mode selected automatically for attached sensor
  • Input voltage: Clamp input: 500 mVrms/50 mVrms; CF 2.8
  • Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
  • Range: 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12\
  • Range: 3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24\
  • Range: 6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36\
  • Range: 40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
  • Bandwidth (-3 dB): 42.5 Hz - 3.5 kHz
  • Scaling: 1:1 and variable
Wireless Connection
  • Number of inputs: 2
  • Supported modules: Fluke Connect® 3000 series
  • Acquisition: 1 reading/s
Data Acquisition
  • Resolution: 16-bit synchronous sampling
  • Sampling frequency: 10.24 kHz at 50/60 Hz, synchronized to mains frequency
  • Input signal frequency: 50/60 Hz (42.5 to 69 Hz)
  • Circuit types: 1-?, 1-? IT, Split phase, 3-? delta, 3-? wye, 3-? wye IT, 3-? wye balanced, 3-? Aron/Blondel (2-element delta), 3-? delta open leg, Currents only (load studies)
  • Data storage: Internal flash memory (not user replaceable)
  • Memory size: Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events
Auxiliary Inputs
  • Number of inputs: 2
  • Input range: 0 to 10 V dc, 1reading/s
  • Scale factor: Format: mx + b (gain and offset) user configurable
  • Displayed units: User configurable (7 characters, for example, °C, psi, or m/s)
Standards Compliance
  • Harmonics: IEC 61000-4-7: Class 1
  • Harmonics: IEEE 519 (short time harmonics)
  • Power quality: IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)
  • Power: IEEE 1459
  • Power quality compliance: EN50160 (for measured parameters)
Voltage Inputs
  • Number of inputs: 4 (3 phases and neutral)
  • Maximum input voltage: 1000 Vrms, CF 1.7
  • Input impedance: 10 M?
  • Bandwidth (-3 dB): 42.5 Hz - 3.5 kHz
  • Scaling: 1:1 and variable
  • Measurement category: 1000 V CAT III/600 V CAT IV
Basic Interval
  • Measured parameters: Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
  • Averaging interval: User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
  • Averaging time min/max values: Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms
Interfaces
  • USB-A: File transfer via USB flash drive, firmware updatesMax. current: 120 mA
  • WiFi: File transfer and remote control via direct connection or WiFi infrastructure
  • Bluetooth: Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1738 or 1736 upgrade option)
  • USB-mini: Data download device to PC
Power Supply
  • Voltage range: 100 V to 500 V using safety plug input when powering from the measurement circuit
  • Voltage range: 100 V to 240 V using standard power cord (IEC 60320 C7)
  • Power consumption: Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)
  • Efficiency: ? 68.2% (in accordance with energy efficiency regulations)
  • Maximum no-load consumption: < 0.3 W only when powered using IEC 60320 input
  • Mains power frequency: 50/60 Hz 15%
  • Battery: Li-ion 3.7 V, 9.25 Wh, customer-replaceable
  • On-battery runtime: Four hours in standard operating mode, up to 5.5 hours in power saving mode
  • Charging time: < 6 hours
Power Quality Measurements
  • Measured parameter: Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD
  • Averaging interval: 10 min
  • Individual harmonics: 2nd to 50th harmonic
  • Total harmonic distortion: Calculated on 50 harmonics
  • Events: Voltage: dips, swells, interruptions, current: inrush current
  • Triggered recordings: Full cycle RMS updated every half cycle of voltage and current (Urms1/2 according to IEC61000-4-30)
  • Triggered recordings: Waveform of voltage and current (1738)
Demand Interval (Energy Meter Mode)
  • Measured parameters: Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
  • Interval: User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off