Product image for LFSE T2000.0020 Reverse Power Relay

Email

LFSE T2000.0020 Reverse Power Relay

Manufacturer: Littelfuse | Catalog # T2000.0020 | Cooper Electric Part # 1045790

$955.63/ea
ea
Log in or register to view your price, purchase history, and more!
Out of stock, please contact your sales representative for availability, pricing and lead times
Reverse Power Relay. 400/450V L-L 5A. Protects the generator from being run as a motor. The Reverse Power Relay T2000 will protect the generator from being run as an electric motor. The T2000 will protect the prime mover of the generator against physical damage, but will also protect the parallel running generators from overload caused by the inversed load shift in a reverse power situation. T2000 reverse power relay function: The T2000 measures the current through an external 5A CT attached on phase L1. The phase angle (phi) is determined from the voltage measurement across L1 and L2. The T2000 calculates the active current as I x cos phi. If the active current becomes negative and exceeds the preset level (2 – 20 percent), the pick-up LED will activate and the trip delay timer (2 – 20 seconds) will also activate. The built-in trip relay will energize after the delay has passed, provided that the preset trip level was continuously exceeded during the time of the delay.

Technical Information

Applications
Industrial
Type
Protection Relays and Controls

Manufacturer Information

Brand
Littelfuse
Sub Brand
Relay Series

General Product Info

12-Digit UPC
079458962468
GTiN
00079458962468
Product UPC
07945896246



Compare