We use essential cookies to make our site work. With your consent, we may also use non-essential cookies to improve user experience and analyze website traffic. By clicking “Accept All,” you agree to our website's cookie use as described in our Cookie Policy, or you can modify your preferences before proceeding.
| Table 250.66 Grounding Electrode Conductor for Alternating-Current System |
|||
| Size of Largest Ungrounded Service-Entrance Conductor or Equivalent Area for Parrell Conductorsa (AWG/kcmil) |
Size of Grounding Electrode Conductor (AWG/kcmil) |
||
| Copper | Aluminum or Copper-Clad Aluminum |
Copper | Aluminum or Copper-Clad Aluminum |
| 2 or smaller | 1 or smaller | 8 | 6 |
| 1 or 1/0 | 2/0 or 3/0 | 6 | 4 |
| 2/0 or 3/0 | 4/0 or 250 | 4 | 2 |
| Over 3/0 through 350 |
Over 250 through 500 |
2 |
1/0 |
| Over 350 through 600 |
Over 500 through 900 |
1/0 | 3/0 |
| Over 600 through 1100 |
Over 900 through 1750 |
2/0 | 4/0 |
| Over 1100 | Over 1750 | 3/0 | 250 |
| Notes: 1. Where multiple sets of service-entrance conductors are used as permitted in 230.40, Exception No.2, the equivalent size of the largest service-entrance conductor shall be determined by the largest sum of the areas of the corresponding conductors of each set. 2. Where there are no service-entrance conductors, the grounding electrode conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served. aThis table also applies to the derived conductors of seperately derived ac systems. bSee installation restrictions in Section 250-64(A). |
|||