We use essential cookies to make our site work. With your consent, we may also use non-essential cookies to improve user experience and analyze website traffic. By clicking “Accept All,” you agree to our website's cookie use as described in our Cookie Policy, or you can modify your preferences before proceeding.
Table C7 (Liquidtight Flexible Metal Conduit) Based on Table 1 Chapter 9 of the 2005 National Electric Code.
| Trade Size in Inches | Wire Size (THWN, THHN) Conductor Size AWG/kcmil | ||||||||||||||||||||
| 14 | 12 | 10 | 8 | 6 | 4 | 3 | 2 | 1 | 1/0 | 2/0 | 3/0 | 4/0 | 250 | 300 | 350 | 400 | 500 | 600 | 700 | 750 | |
| 1/2 | 13 | 9 | 6 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| 3/4 | 22 | 16 | 10 | 6 | 4 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | --- | --- | --- | --- | --- | --- | --- | --- |
| 1 | 36 | 26 | 16 | 9 | 7 | 4 | 3 | 3 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | --- | --- | --- | --- | --- |
| 1-1/4 | 63 | 46 | 29 | 16 | 12 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | --- |
| 1-1/2 | 81 | 59 | 37 | 21 | 15 | 9 | 8 | 7 | 5 | 4 | 3 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
| 2 | 133 | 97 | 61 | 35 | 25 | 15 | 13 | 11 | 8 | 7 | 6 | 5 | 4 | 3 | 3 | 2 | 1 | 1 | 1 | 1 | 1 |
| 2-1/2 | 201 | 146 | 92 | 53 | 38 | 23 | 20 | 17 | 12 | 10 | 8 | 7 | 6 | 5 | 4 | 3 | 3 | 2 | 1 | 1 | 1 |
| 3 | 308 | 225 | 141 | 81 | 59 | 36 | 30 | 26 | 19 | 16 | 13 | 11 | 9 | 7 | 6 | 5 | 5 | 4 | 3 | 3 | 3 |
| 3-1/2 | 401 | 292 | 184 | 106 | 76 | 47 | 40 | 33 | 25 | 21 | 17 | 14 | 12 | 10 | 8 | 7 | 6 | 5 | 4 | 4 | 3 |
| 4 | 523 | 381 | 240 | 138 | 100 | 61 | 52 | 44 | 32 | 27 | 23 | 19 | 15 | 12 | 11 | 9 | 8 | 7 | 6 | 5 | 5 |